Mains Failure: 3-attempt engine cranking after mains failure otherwise the engine fails to start. Engine start-up within 10 sec of mains failure otherwise 2 more start pulses after every 10-15 seconds
Unhealthy Mains: Any of the phase failure or voltage drops below set value
Mains Restoration: Engine keeps running for 30 seconds before stopping, as recommended by the Engine manufacturer
Metering
One Ammeter with CTs & selector switch, one frequency meter, one voltmeter with selector switch and one hour meter
Set of indications
- Load on DG
- Load on mains
- Fault indications
- LLOP
- High water temp/high cylinder head temp
- Overload
Set of Push Buttons
- Engine start/stop
- Alarm acknowledge button for hooter
- Reset button for fault indication
Safety
- High water temperature
- Overload trip
Battery Charger: A separate battery charger for continuous charging of batteries in trickle/boost mode to ensure prompt starting of the engine